Overview
Category | Details |
---|---|
Presentation | Highly efficient, easy-to-deploy 30kW, 400V 3-phase UPS. Suitable for edge, small/medium data centers, and critical infrastructure. Marine certified. |
Includes 5×8 start-up service and halogen-free cables. | |
Lead time | Usually Ships within 2 Weeks |
Main
Parameter | Value |
---|---|
Main Input Voltage | 400 V 3 phase |
Other Input Voltage | 380 V, 415 V |
Main Output Voltage | 400 V 3 phase |
kW Rating | 30 kW |
Rated Power in VA | 30 kVA |
Battery Type | External battery system, Li-Ion, VRLA |
Provided Equipment | Dust filter, EcoStruxure IT ready (UPS), Installation guide, Integrated network management, Power modules ship installed, Start-Up Service |
Range of Product | Galaxy VS |
Range Compatibility | Galaxy VS |
Batteries & Runtime
Parameter | Value |
---|---|
Battery Voltage | 480ā576 VDC |
End of Discharge Battery Voltage | 307 V DC |
End of Discharge Maximum Battery Current | 102 A |
Battery Power in VAH | 0 VAh runtime |
Extendable Run Time | 0 |
General
Parameter | Value |
---|---|
Bypass Voltage Tolerance | +/- 10 % |
Redundant | No |
Product/Component Type | Uninterruptible Power Supply (UPS) |
Physical
Parameter | Value |
---|---|
Color | White |
Height | 58.46 in (148.5 cm) |
Width | 2.05 in (52.1 mm) |
Depth | 33.35 in (84.7 cm) |
Product Weight | 454.2 lb (206 kg) |
USB Compatible | No |
Input
Parameter | Value |
---|---|
Input Frequency | 40 – 70 Hz |
Efficiency at Full Load | 340…460 V 400 V |
Max Input Current per Phase | 54 A |
Max Short Circuit Withstand (Icw) | 65 kA |
Input Total Harmonic Distortion | < 3% at full load |
Load Power Factor | 0.7 leading to 0.7 lagging (no derating) |
Output
Parameter | Value |
---|---|
Max Configurable Power (Watts) | 30 kW |
Output Frequency | 50/60 Hz (sync to mains), +/-0.1% not synced |
Crest Factor | 2.5 |
Waveform Type | Sine wave |
Output Voltage Tolerance | +/-1% after 50 ms |
Output Voltage THD | < 1% (linear), < 5% (non-linear) |
Overload Operation | 10 min @ 125%, 60 sec @ 150% |
Bypass Type | Built-in Static Bypass |
Max Configurable Power in VA | 30 kVA |
Conformance
Standards |
---|
EN/IEC 62040-1, EN/IEC 62040-2, FCC Part 15 class A, IEC 60721-4-2 Level 2M2, UL 1778 5th edition |
Environmental
Parameter | Value |
---|---|
Ambient Operating Temp | 32ā¦104 °F (0ā¦40 °C) |
Relative Humidity (Operation) | 0ā95% non-condensing |
Operating Altitude | 0ā3300 ft |
Storage Temperature | -13ā¦131 °F (-25ā¦55 °C) |
Storage Relative Humidity | 10ā80% non-condensing |
Acoustic Level | 68 dBA |
Online Thermal Dissipation | 3122 Btu/h |
IP Degree of Protection | IP21 |
There are no reviews yet.