Galaxy VS UPS 30kW 400V for external batteries, halogen-free cables, marine certified, Start-up 5×8


AED163,299.00

Overview

Category Details
Presentation Highly efficient, easy-to-deploy 30kW, 400V 3-phase UPS. Suitable for edge, small/medium data centers, and critical infrastructure. Marine certified.
Includes 5×8 start-up service and halogen-free cables.
Lead time Usually Ships within 2 Weeks

Main

Parameter Value
Main Input Voltage 400 V 3 phase
Other Input Voltage 380 V, 415 V
Main Output Voltage 400 V 3 phase
kW Rating 30 kW
Rated Power in VA 30 kVA
Battery Type External battery system, Li-Ion, VRLA
Provided Equipment Dust filter, EcoStruxure IT ready (UPS), Installation guide, Integrated network management, Power modules ship installed, Start-Up Service
Range of Product Galaxy VS
Range Compatibility Galaxy VS

Batteries & Runtime

Parameter Value
Battery Voltage 480–576 VDC
End of Discharge Battery Voltage 307 V DC
End of Discharge Maximum Battery Current 102 A
Battery Power in VAH 0 VAh runtime
Extendable Run Time 0

General

Parameter Value
Bypass Voltage Tolerance +/- 10 %
Redundant No
Product/Component Type Uninterruptible Power Supply (UPS)

Physical

Parameter Value
Color White
Height 58.46 in (148.5 cm)
Width 2.05 in (52.1 mm)
Depth 33.35 in (84.7 cm)
Product Weight 454.2 lb (206 kg)
USB Compatible No

Input

Parameter Value
Input Frequency 40 – 70 Hz
Efficiency at Full Load 340…460 V 400 V
Max Input Current per Phase 54 A
Max Short Circuit Withstand (Icw) 65 kA
Input Total Harmonic Distortion < 3% at full load
Load Power Factor 0.7 leading to 0.7 lagging (no derating)

Output

Parameter Value
Max Configurable Power (Watts) 30 kW
Output Frequency 50/60 Hz (sync to mains), +/-0.1% not synced
Crest Factor 2.5
Waveform Type Sine wave
Output Voltage Tolerance +/-1% after 50 ms
Output Voltage THD < 1% (linear), < 5% (non-linear)
Overload Operation 10 min @ 125%, 60 sec @ 150%
Bypass Type Built-in Static Bypass
Max Configurable Power in VA 30 kVA

Conformance

Standards
EN/IEC 62040-1, EN/IEC 62040-2, FCC Part 15 class A, IEC 60721-4-2 Level 2M2, UL 1778 5th edition

Environmental

Parameter Value
Ambient Operating Temp 32…104 °F (0…40 °C)
Relative Humidity (Operation) 0–95% non-condensing
Operating Altitude 0–3300 ft
Storage Temperature -13…131 °F (-25…55 °C)
Storage Relative Humidity 10–80% non-condensing
Acoustic Level 68 dBA
Online Thermal Dissipation 3122 Btu/h
IP Degree of Protection IP21

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Galaxy VS UPS 30kW 400V for external batteries, halogen-free cables, marine certified, Start-up 5×8”

There are no reviews yet.