APC Symmetra RM 6kVA Scalable to 6kVA N+1 208/240V w/ 208 to 120V Step-Down Transformer (4) L5-20R


AED92,499.00

Overview

Attribute Value
Lead Time Usually in Stock
Product or Component Type Uninterruptible Power Supply (UPS)
Range of Product Symmetra
Run Time for Load 12 min 37 s (at 4200 W)
Load Range 420–4200 W
Max Capacity Used 100%
Main Input Voltage 208 V
Main Output Voltage 120 V / 208 V
kW Rating 4200 W
Rated Power in VA 6000 VA
Input Connection Type NEMA L6-30P 30 A
Output Connection Type 4 NEMA L5-20R, 2 NEMA L6-20R
Number of Rack Units 10U
Cable Length 10 ft (3.05 m)
Number of Cables 1
Battery Type Lead-Acid battery
Provided Equipment User Manual, Rack Mounting Brackets, Rails, CD
USB Compatible No

Batteries & Runtime

Attribute Value
Included Battery Modules 3
Battery Slots Empty 0
Typical Recharge Time 3 hours
Configurable Output Voltage 208 or 240 V nominal
Battery Charge Power 610 W rated
Battery Life 3–5 years
Extendable Runtime Yes (1 additional pack supported)

General

Attribute Value
Product Web Sub-family 2kVA power increments
Number of Power Modules 4
Preinstalled Power Modules 3
Power Module Free Slots 0
Power Module Filled Slots 0
Redundant Yes

Physical

Attribute Value
Color Black
Height 17.52 in (44.5 cm)
Width 19.02 in (48.3 cm)
Depth 28.74 in (73 cm)
Net Weight 389.82 lb (176.82 kg)
Mounting Location Front
Mounting Preference Lower
Mounting Mode Rack-mounted
Two-Post Mountable No

Input

Attribute Value
Input Frequency 60 Hz ± 3 Hz
Number of Input Connectors 1 Hard Wire (3-wire: 2PH + G)
Input Voltage Range 155–276 V
Input Power Factor at Full Load 0.98

Output

Attribute Value
Max Configurable Power (Watts) 4200 W
Max Configurable Power (VA) 6000 VA
Harmonic Distortion < 5% at full load
Output Frequency (sync to mains) 57–63 Hz (for 60 Hz nominal)
Output Frequency (not synced) 60 Hz ± 0.1%
Crest Factor Up to 5:1
Topology Double Conversion Online
Wave Type Sine wave
Bypass Type Internal (Automatic and Manual)
Efficiency at Full Load 85%

Conformance

Attribute Value
Product Certifications CSA
Standards FCC Part 15 Class A, UL 1778

Environmental

Attribute Value
Operating Temperature 32–104 °F (0–40 °C)
Relative Humidity (Operating) 0–95% RH
Operating Altitude 0–10,000 ft
Storage Temperature 5–113 °F (-15–45 °C)
Relative Humidity (Storage) 0–95% RH
Storage Altitude 0–50,000 ft (0–15,240 m)
Acoustic Level 60 dBA
Online Thermal Dissipation 2529 Btu/h

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “APC Symmetra RM 6kVA Scalable to 6kVA N+1 208/240V w/ 208 to 120V Step-Down Transformer (4) L5-20R”