Category | Detail |
---|
Overview | A highly efficient, modular, 800 kVA 3-phase UPS for large data centers and mission-critical applications. Up to 99% efficiency in eConversion mode. Includes 5×8 start-up service. |
Lead Time | Special Order – Call for Quoted Lead Times |
Main |
Main Input Voltage | 400 V 3 phase |
Main Output Voltage | 400 V 3 phase |
kW Rating | 800 kW |
Rated Power in VA | 800 kVA |
Battery Type | External battery system |
Provided Equipment | Installation guide, Start-Up Service |
Range of Product | Galaxy VX |
Range Compatibility | Galaxy VX |
Batteries & Runtime |
Battery Voltage | 480 V |
End of Discharge Battery Voltage | 384 V DC |
Battery Power in VAH | 0 VAh runtime |
Extendable Run Time | 0 |
General |
Redundant | No |
Product or Component Type | Uninterruptible power supply (UPS) |
Physical |
Color | White |
Width | 141.73 in (360 cm) |
Product Weight | 6856.4 lb(US) (3110 kg) |
USB Compatible | No |
Input |
Input Frequency | 40 – 70 Hz |
Max Input Current per Phase | 1361 A |
Load Power Factor | From 0.7 leading to 0.5 lagging without derating |
Output |
Max Configurable Power (Watts) | 800 kW |
Output Frequency | 50 Hz/60 Hz sync to mains; 50 Hz ±0.1% (not synced) |
Crest Factor | 3 with THC <5% |
Waveform Type | Sine wave |
Overload Operation | 10 min @ 125%, 60 sec @ 150% |
Max Configurable Power (VA) | 800 kVA |
Conformance |
Product Certifications | C-tick, CE |
Standards | EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, IBC 2012, IEC 62040-4, ISTA 2B |
Environmental |
Ambient Air Temp. for Operation | 32ā¦104 °F (0ā¦40 °C) |
Relative Humidity | 0ā¦95 % |
Operating Altitude | 0…3333 ft |
Storage Relative Humidity | 0ā¦95 % non-condensing |
Acoustic Level | 69.5 dB |
Online Thermal Dissipation | 128,620 Btu/h |
IP Degree of Protection | IP20 |
There are no reviews yet.