Category
|
Description/Value
|
---|---|
Overview
|
|
Presentation
|
Highly efficient, easy-to-deploy 40kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5×8 start-up service and halogen-free cables. Marine certified.
|
Lead time
|
Usually Ships within 2 Weeks
|
Main
|
|
Main Input Voltage
|
400 V 3 phase
|
Other Input Voltage
|
380V, 415V
|
Main Output Voltage
|
400 V 3 phase
|
Kw Rating
|
40 kW
|
Rated power in VA
|
40 kVA
|
Battery Type
|
External battery system, Li-Ion (Lithium Ion), VRLA
|
Provided equipment
|
Dust filter, EcoStruxure IT ready (UPS), Installation guide, Integrated network management, Power modules ship installed, Start-Up Service
|
Range of Product
|
|
Product Range
|
Galaxy VS
|
Range Compatibility
|
|
Compatible Range
|
Galaxy VS
|
Batteries & Runtime
|
|
Battery Voltage
|
480-576VDC
|
End of Discharge Battery Voltage
|
307 V DC
|
End of Discharge Maximum Battery Current
|
136 A
|
Battery power in VAH
|
0 VAh runtime
|
Extendable Run Time
|
0
|
General
|
|
Bypass Voltage Tolerance
|
+/- 10 %
|
Redundant
|
No
|
Product or Component Type
|
Uninterruptible power supply (UPS)
|
Physical
|
|
color
|
White
|
Height
|
58.46 in (148.5 cm)
|
Width
|
2.05 in (52.1 mm)
|
Depth
|
33.35 in (84.7 cm)
|
Product Weight
|
454.2 lb(US) (206 kg)
|
USB compatible
|
No
|
Input
|
|
Input Frequency
|
40 – 70 Hz
|
Efficiency at full load
|
340…460 V 400 V
|
Maximum Input Current per Phase
|
72 A
|
Maximum Short Circuit Withstand (Icw)
|
65 kA
|
Input Total Harmonic Distortion
|
Less than 3% for full load
|
Load power factor
|
From 0.7 leading to 0.7 lagging without any derating
|
Output
|
|
Max Configurable Power (Watts)
|
40 kW
|
Output frequency
|
50 Hz sync to mains, 60 Hz sync to mains, 50 Hz +/- 0.1 % for 50 Hz nominal not synced, 60 Hz +/- 0.1 % for 60 Hz nominal not synced
|
Crest factor
|
2.5
|
Waveform Type
|
Sine wave
|
Output voltage tolerance
|
+/-1% after 50ms
|
Output Voltage THD
|
< 1% linear load and < 5% non-linear load
|
Overload Operation
|
10 minutes @ 125% and 60 seconds @ 150%
|
Bypass type
|
Built-in Static Bypass
|
Maximum configurable power in VA
|
40 kVA
|
Conformance
|
|
Standards
|
EN/IEC 62040-1, EN/IEC 62040-2, FCC Part 15 class A, IEC 60721-4-2 Level 2M2, UL 1778 5th edition
|
Environmental
|
|
Ambient air temperature for operation
|
32ā¦104 °F (0ā¦40 °C)
|
Relative Humidity
|
0ā¦95 % non-condensing
|
Operating altitude
|
0…3300 ft
|
Ambient Air Temperature for Storage
|
-13ā¦131 °F (-25ā¦55 °C)
|
Storage Relative Humidity
|
10ā¦80 % non-condensing
|
Acoustic level
|
68 dBA
|
Online Thermal Dissipation
|
4333 Btu/h
|
IP degree of protection
|
IP21
|
UPS , Power Back up and accessories
Galaxy VS UPS 40kW 400V for external batteries, halogen-free cables, marine certified, Start-up 5×8
AED178,299.00
There are no reviews yet.