Overview
Item | Description |
---|---|
Presentation | Highly efficient, easy-to-deploy 80kW, 400V 3-phase UPS for edge, small/medium data centers, commercial, and industrial applications. Includes 5×8 start-up service and halogen-free cables. Marine certified. |
Lead Time | Usually ships within 2 weeks |
Main Electrical Specifications
Parameter | Value |
---|---|
Main Input Voltage | 400 V 3 phase |
Other Input Voltage | 380 V / 415 V |
Main Output Voltage | 400 V 3 phase |
kW Rating | 80 kW |
Rated Power in VA | 80 kVA |
Battery Type | External, Li-Ion, VRLA |
Provided Equipment
Included |
---|
Dust filter |
EcoStruxure IT ready (UPS) |
Installation guide |
Integrated network management |
Power modules ship installed |
Start-Up Service |
Product Range
Range | Compatibility |
---|---|
Galaxy VS | Galaxy VS |
Batteries & Runtime
Parameter | Value |
---|---|
Battery Voltage | 384ā576 V DC |
End of Discharge Voltage | 307 V DC |
Max Discharge Battery Current | 217 A |
Battery Power | 0 VAh runtime |
Extendable Runtime | No |
General Features
Parameter | Value |
---|---|
Bypass Voltage Tolerance | ±10% |
Redundant | No |
Product Type | Uninterruptible Power Supply (UPS) |
Physical Specifications
Attribute | Value |
---|---|
Color | White |
Height | 58.46 in (148.5 cm) |
Width | 2.05 in (52.1 mm) |
Depth | 33.35 in (84.7 cm) |
Weight | 551.2 lb (250 kg) |
USB Compatible | No |
Input Specifications
Parameter | Value |
---|---|
Input Frequency | 40 ā 70 Hz |
Efficiency at Full Load | 340ā460 V @ 400 V |
Max Input Current per Phase | 144 A |
Max Short Circuit Withstand (Icw) | 65 kA |
Input THD | < 3% at full load |
Load Power Factor | 0.7 leading to 0.7 lagging |
Output Specifications
Parameter | Value |
---|---|
Max Configurable Power (W / VA) | 80 kW / 80 kVA |
Output Frequency | 50 Hz / 60 Hz (sync to mains) |
Frequency Accuracy (Not Synced) | ±0.1% for 50/60 Hz |
Crest Factor | 2.5 |
Waveform Type | Sine wave |
Output Voltage Tolerance | ±1% after 50ms |
Output Voltage THD | < 1% linear load, < 5% non-linear load |
Overload Operation | 10 min @ 125%, 60 sec @ 150% |
Bypass Type | Built-in Static Bypass |
Environmental Conditions
Condition | Value |
---|---|
Operating Temp | 32 ā 104 °F (0 ā 40 °C) |
Operating Relative Humidity | 0 ā 95%, non-condensing |
Operating Altitude | 0 ā 3300 ft |
Storage Temp | -13 ā 131 °F (-25 ā 55 °C) |
Storage Relative Humidity | 10 ā 80%, non-condensing |
Acoustic Level | 68 dBA |
Online Thermal Dissipation | 8394 Btu/h |
IP Degree of Protection | IP21 |
Conformance & Standards
Standard / Certification |
---|
EN/IEC 62040-1 |
EN/IEC 62040-2 |
FCC Part 15 Class A |
IEC 60721-4-2 Level 2M2 |
UL 1778 5th Edition |
There are no reviews yet.