Galaxy VS UPS 40kW 400V for external batteries, halogen-free cables, marine certified, Start-up 5×8


AED178,299.00

Category
Description/Value
Overview
Presentation
Highly efficient, easy-to-deploy 40kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5×8 start-up service and halogen-free cables. Marine certified.
Lead time
Usually Ships within 2 Weeks
Main
Main Input Voltage
400 V 3 phase
Other Input Voltage
380V, 415V
Main Output Voltage
400 V 3 phase
Kw Rating
40 kW
Rated power in VA
40 kVA
Battery Type
External battery system, Li-Ion (Lithium Ion), VRLA
Provided equipment
Dust filter, EcoStruxure IT ready (UPS), Installation guide, Integrated network management, Power modules ship installed, Start-Up Service
Range of Product
Product Range
Galaxy VS
Range Compatibility
Compatible Range
Galaxy VS
Batteries & Runtime
Battery Voltage
480-576VDC
End of Discharge Battery Voltage
307 V DC
End of Discharge Maximum Battery Current
136 A
Battery power in VAH
0 VAh runtime
Extendable Run Time
0
General
Bypass Voltage Tolerance
+/- 10 %
Redundant
No
Product or Component Type
Uninterruptible power supply (UPS)
Physical
color
White
Height
58.46 in (148.5 cm)
Width
2.05 in (52.1 mm)
Depth
33.35 in (84.7 cm)
Product Weight
454.2 lb(US) (206 kg)
USB compatible
No
Input
Input Frequency
40 – 70 Hz
Efficiency at full load
340…460 V 400 V
Maximum Input Current per Phase
72 A
Maximum Short Circuit Withstand (Icw)
65 kA
Input Total Harmonic Distortion
Less than 3% for full load
Load power factor
From 0.7 leading to 0.7 lagging without any derating
Output
Max Configurable Power (Watts)
40 kW
Output frequency
50 Hz sync to mains, 60 Hz sync to mains, 50 Hz +/- 0.1 % for 50 Hz nominal not synced, 60 Hz +/- 0.1 % for 60 Hz nominal not synced
Crest factor
2.5
Waveform Type
Sine wave
Output voltage tolerance
+/-1% after 50ms
Output Voltage THD
< 1% linear load and < 5% non-linear load
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Bypass type
Built-in Static Bypass
Maximum configurable power in VA
40 kVA
Conformance
Standards
EN/IEC 62040-1, EN/IEC 62040-2, FCC Part 15 class A, IEC 60721-4-2 Level 2M2, UL 1778 5th edition
Environmental
Ambient air temperature for operation
32…104 °F (0…40 °C)
Relative Humidity
0…95 % non-condensing
Operating altitude
0…3300 ft
Ambient Air Temperature for Storage
-13…131 °F (-25…55 °C)
Storage Relative Humidity
10…80 % non-condensing
Acoustic level
68 dBA
Online Thermal Dissipation
4333 Btu/h
IP degree of protection
IP21

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Galaxy VS UPS 40kW 400V for external batteries, halogen-free cables, marine certified, Start-up 5×8”